Simplex | 4090-9051-RC - Protegis Fire & Safety Skip to content
Skip to content

Simplex | 4090-9051-RC

RECON-Idnet E-Series Supervised Iam

SKU SP-F1P1-6458-RC
$74.99
Availability: Only 2 left!

Model 4090-9051 Encapsulated Switch Module

General Features:

  • Encapsulated Design: Built to withstand extended exposure to high humidity conditions. This model does not include a status indicating LED.

  • Color-Coded Leads: Equipped with color-coded 18 AWG leads for easy wiring.

IDNet Communications:

  • Tamper and Waterflow Monitoring: Provides current-limited monitoring of a tamper switch (supervisory) and waterflow switch (alarm) on the same circuit, utilizing a single point.

  • Available with IDNet Communications Only: This module operates exclusively with IDNet communications.

Multiple Operation Modes:

  • Contact Closure Status: Allows tracking of contact closure status.

  • Momentary Contact Closure: Enables selection of momentary contact closure conditions at the panel to be latched or tracked (note that this option is not available with the 2120 CDT).

UL Listed: Meets the requirements of Standard 864.

Electrical:

  • Power and Communications: Supports both MAPNET II or IDNet, automatically selected, with one address per IAM.

  • Input Requirements: Accepts normally open, dry contacts.

Wire Connections:

  • 4090-9051: Features color-coded wire leads, 18 AWG (0.82 mm²), with an 8” (203 mm) length.

Wiring Distances:

  • Distance from IAM to Contacts: Maximum of 500 ft (152 m) without protectors, or 400 ft (122 m) maximum with the 2081-9044 Overvoltage Protectors.

  • Wiring Distance Reference (per channel) for MAPNET II or IDNet Communications: Maximum of 2500 ft (762 m) from the fire alarm control panel, with a total wiring distance of up to 10,000 ft (3048 m) (including T-Taps).

Mechanical:

  • Dimensions: 1-9/16” W x 1-9/16” H x 9/16” D (40 mm x 40 mm x 14 mm).

  • Temperature Range: Designed for indoor operation within a temperature range of 32° to 158° F (0° to 70° C).

  • Humidity Range: Suitable for operation in environments with humidity levels of up to 93% RH at 100° F (38° C).